Model |
Input
Voltage |
Output
Voltage |
Output
Current |
Output
Power |
GWH110/24/20,8
|
77-162.5V DC |
24V |
20.8A |
500 Watt |
GWH110/48/10,4
|
77-162.5V DC |
48V |
10.4A |
500 Watt |
GWH110/60/8,3
|
77-162.5V DC |
60V |
8.3A |
500 Watt |
Input:
Input DC see table
Making current limitation I max < I nom
Maximum permissible
superimposed AC voltage
of voltage source Ue ∼≤5%
Maximum activation
delay (including run-up) Tv < 2 Sec.
Overcurrent protection safety fuse in input circuit
Overvoltage protection Varistor in input circuit
Polarity reversal protection Polarity reversal protection device in input
circuit
Output:
Direct output voltage see table
Output currents see table
Output decoupling diode is built into the device.
The anode side of the decoupling diode is also led to the output terminal.
Control data:
Load control < 0.1%
Mains control < 0.1%
Superimposed AC voltage
(measuring bandwidth
30 Mhz) ≤ 1%
Undershoot /
overshoot at load
changes of 10 - 90% ≤ 5%
Protection and monitoring equipment:
Overload protection U-I characteristic curve current limitation
Activation point: 1.1 x I nom
Sensor line operation Wrong sensor line connections do not
damage the converter.
In the event of a sensor line break the
output voltage is limited to a maximum of
120% of the nominal output voltage.
1 V adjustable.
Overtemperature protection Shut-off if temperature becomes too high,
automatic reactivation when temperature
drops
Varistor in output as additional overtemperature protection.
Signalling relay in output with volt-free changeover contact.
Output voltage monitored for undervoltage and overvoltage.
Operating parameters:
Operating temperature range -25°C - 70°C (derating from +50°C with
2%/K)
Cooling From built-in fan, temperature controlled
Safety:
Primary -> secondary 3kV 50 Hz
Primary -> housing 2kV 50 Hz
Secondary -> housing 2kV 50 Hz
Electrical safety VDE 0805 EN60950
Protection class 1
EMC:
EN61000-6-1 to EN61000-6-4
Control, operating and indicating elements:>
Indicators There is an LED at the connection sidefor indicating
the presence of the input voltage.
A second LED indicates output voltage within range.
A third LED indicates temperature too high
Output voltage adjustment The output voltage can be adjusted using
a potentiometer at the connection side
The adjusting range is +5% -10%.
Parallel switching capability 3 units can be operated in parallel to
increase output.
An internal current sharing circuit is
mainly responsible for this.
Sensor line operation 1 V, adjustable
Electrical connections:
10mm² screw terminals for input and 4mm² for output (double)
1.5mm² screw terminals for signalling
Mechanical configuration:
Dimensions: WxHxD, 225 x 125 x 125
The standard version of the converter is housed in an aluminium case.
The screw terminals enable fast and simple connection.
The 125mm height means the converter can be also installed in a 19" rack.
The surface of the converter is finished in white chrome.
A ruggedised version of the converter is also available for railway applications.
Option: vibration-proof.
|